USAID/HAITI Pilot Project for Sustainable
Electricity Distribution (PPSELD)
Closeout Report
Prepared by
NRECA International
for USAID Contract
No. 72052120C00002
February 2022
NRECA International Page ii
Contents
List of Acronyms and Abbreviations ........................................................................................................... iii
Executive Summary ..................................................................................................................................... iv
Introduction ................................................................................................................................................... 1
Task 1 Provide Reliable and Efficient Electricity Service ............................................................................ 2
Commercial and customer service department ........................................................................................... 2
Electricity delivered, sales and losses ........................................................................................................ 3
Tariffs…………….. ................................................................................................................................... 7
Customer Service - Meters reading, billing and collections. ...................................................................... 9
Task 2 Operate and maintain the 10 MW generation plant, distribution grid, and ancillary equipment .... 12
Electricity power generation plant ........................................................................................................... 12
Preventive maintenance ............................................................................................................................ 15
Laboratory tests ........................................................................................................................................ 18
Electricity Distribution System ................................................................................................................ 18
Task 3. Reduce Non- technical Electricity Loss by Increasing Metered Customers. .................................. 22
Customer normalization and connection of new clients ........................................................................... 22
Electricity loss reduction program ........................................................................................................... 23
Task 4 Facilitate transition to future private operator. ................................................................................ 25
NRECA International Page iii
List of Acronyms and Abbreviations
CCEP Caracol Community Electrification Program
CIP Caracol Industrial Park
EdH Electricite d’Haiti
GIS Geographic Information System
GOH Government of Haiti
HTG Haiti Gourde
IDB InterAmerican Development Bank
kWh Kilowatt- hours
LV Low Voltage
MV Medium Voltage
MW Megawatts
MWh Megawatt hours
NRECA NRECA International
PPSELD Pilot Project for Sustainable Electricity Distribution
USAID United States Agency for International Development
USD United States Dollars
NRECA International Page iv
Executive Summary
The Government of Haiti ( GoH), with the support of USAID, is implementing a program to expand
the electrification of Haiti. This program aims to attract private investment for the 10 regional
departments, including the Project for Sustainable Electricity Distribution - PPSELD service area.
In 2020, USAID and NRECA International (NRECA) signed a contract for the continued
management and operation of the PPSELD utility. This contract period is called the Project for
Sustainable Electricity Distribution - Transition, or PSELD-T.
The most significant event that affected the operations of PPSELD in the two years of project
implementation was the COVID-19 pandemic. PSELD-T adopted and implemented social
distancing and hygiene protocols issued by the health authorities, and other measures to ensure the
safety of PPSELD clients and employees.
Despite COVID-19 restrictions, NRECA continued to comply with the technical, operational,
commercial and customer service requirements to ensure efficient operation of the PPSELD utility.
As a result, very high levels of service quality and reliability were achieved and maintained through
PSELD-T project period. High levels of performance were maintained for quality of electricity
service, collection rates as well as loss control
The PSELD-T project consisted of four tasks designed to ensure high levels of performance in
preparation for the transfer of utility management from NRECA to a new, private operator. Task
1 was focused to provide reliable and efficient electricity service thr oughout the PPSELD utility
service area. To achieve this objective, NRECA team members oversaw local PPSELD utility
generation and distribution administrative, operational and commercial staff to ensure excellence
in distribution system operation, billing and collections, loss management, and multiple customer
service activities including connection of new consumers, disconnections, registration of
complaints and addressing customer complaints in a timely fashion .
Task 2 focused on operat ion, repair, and maintenance of the generation plant. At the outset of the
PSELD-T contract, NRECA was forced to take full, direct responsibility for the PPSELD
powerplant due to the decision of the former sub- contractor not to participate in PSELD-T.
NRECA retained most of the PPSELD personnel for PSELD-T, hired a new generation plant
supervisor and directed all power plant operations, preventative and corrective maintenance, as
well as staff training and performance monitoring for the generation plant. Throughout the
PSELD-T project period, the PPSELD power plant remained the most reliable power plant in Haiti
with an average service availability index ( ASAI) of 99.66% for the year of 2020 and 99.75% for
the year of 2021.
Task 3 focused on reduction of technical and non -technical losses. Due to the COVID- 19 pandemic
during this period of PSELD-T contract, the activities of the revenue protection crews were
significantly restricted. However, disconnections of illegal connections and theft control remained
a necessary and essential project activity. Through January 2022, 768 illegal connections were
disconnected, and 182 cases of electricity theft were discovered. Electricity losses during the 24
months remained stable at an average of 11.5%. Losses withi n the CIP averaged around 5%, while
losses outside the park were 15% to 16%.
NRECA International Page v
Task 4 was defined as a support activity in which NRECA was required to f acilitate the transition
to management by a private operator. The GoH continued to implement its strategy to privatize
the electricity service in the 10 departments of Haiti, including the PPSELD service area. To
comply with this task, the NRECA team provided periodic to the USAID technical team including
provision of data and info rmation regarding PPSELD operations. Unfortunately, negotiations with
leading candidates did move forward and the GoH decided to abandon negotiations in October
2021. A new tender process was expected in 2022.
Considering current economic and political conditions in the country and the Haitian electricity
market, PSELD-T has achieved remarkab le success. Overall revenue recovery allowed PPSELD
to cover fuel, local labor, and other operating costs. Power reliability and availability continued on
par with high- performing electric utilities in Latin America and the Caribbean. Due to the
devaluation of the Haitian Gourde (HTG) , the current tariffs do not provide for the total recovery
of PPSELD operating costs. Going forward, tariffs rates should be indexed in a way to provide for
full cost recovery and adjust to the fluctuations in the international fuel markets.
NRECA International Page 1
Project for Sustainable Electricity Distribution Transition (PSELD-T):
Closeout Report
Introduction
USAID awarded NRECA International the contract to implement the Pilot Project for Sustainable
Electricity Distribution (PPSELD) in May 2013. The PPSELD project was an initiative to establish
a generation and distribution electricity utility in n ortheast Haiti to provide reliable and sustainable
electric service. The primary task of P PSELD was to operate a 10MW HFO-diesel power plant
located in the Caracol Industrial Park (CIP), to commercialize power within the CIP to industrial
clients in the CIP, and to expand electricity service to residential and small commercial customers
outside the CIP in several communes that are in the vicinity of the CIP, Caracol, Terrier Rouge,
Trou du Nord, Limonade and Saint Suzanne.
The GoH with the support of USAID began a process to attract private investors to engage in
concession agreements to operate electric power facilities in ten departments in Haiti. The
PPSELD service area is included in this program. In recognition of this program, USAID designed
a transition project that was awarded to NRECA as the legacy contractor to the PPSELD project.
This transition project is called Project for Sustainable Electricity Distribution - Transition,
PSELD-T.
The most significant event that affected the operations of PSELD-T in these two years was the
COVID- 19 pandemic that affected Haiti as it did all countries throughout the world. Although
Haiti did not report infection rates as high as many other countries in Latin America and the
Caribbean, restrictions taken to reduce the spread of COVID-19 significantly affected all PSELD -
T activities. PSELD-T implemented the social distancing and hygiene protocols issued by the
health authorities. For this purpose, PSELD -T implemented a policy for employee compliance.
Despite the restrictions, NRECA continued to comply with the technical, operational, commercial
and customer service policies and procedures implemented for an efficient operation of the electric
company. As a result, very high levels of service quality and reliability were maintained, high
levels of collection. Despite the limitations to continue with all the inspection actions to control
the theft of electricity in the users' homes and the impact on the users' economy, the level of losses
was controlled and did not increase.
This scope of work for PSELD-T includes four main tasks that are summarized in Table 1 below.
Table 1 Description of the tasks to be implemented
Task Number Task Summary Name
Task 1 Provide reliable and efficient electricity services
Task 2 Operate and maintain the 10 MW generation plant, distribution grid, and ancillary equipment.
Task 4 Facilitate transition to future private operator.
Task 3 Reduce non-technical electricity loss by increasing metered customers
NRECA International Page 2
This document presents the closeout report of the PSELD-T project. The report describes the tasks
and activities undertaken by NRECA on behalf of USAID as well as the results achieved over the
two years of project implementation. NRECA submitted monthly and semi -annual progress reports
that summarized activity challenges and results throughout the PPSELD implementation period.
Task 1 Provide Reliable and Efficient Electricity Service
Commercial and c ustomer service department
The activities of the commercial and customer service department were focused on billing and
collection, connections and disconnections, and attention to customer needs and concerns. The
commercial/customer service team members were responsible for all facets of customer service,
meter reading, billing, collections receiving and processing applications for service, service
connections and disconnections. In addition, commercial/customer service team members
managed customer education and communications des igned to promote understanding of PPSELD
utility operations and to build a bridge of trust with the communities served by PPSELD. T he
commercial/customer service department also continued to manage an aggressive loss control
program, carrying out activities to detect theft by customers and illegal connections.
CIP clients
During the last two years of the project, the number of clients in the CIP remained unchanged as
shown in Table 2.
Table 2. CIP client count by month and by year.
Year Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
2020 11 11 11 11 13 11 11 11 14 13 12 11
2021 11 11 11 11 11 11 11 11 11 11 11 11
2022 11
Year Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
2020 11 11 11 11 13 11 11 11 14 13 12 11
2021 11 11 11 11 11 11 11 11 11 11 11 11
2022 11
Residential and commercial clients outside CIP
Residential clients represent 97% of all clients at PSELD, 2% of the clients are commercial and
1% public facilities . Over the course of PSELD-T, the number of non- CIP clients has increased
in number as shown in Table 3. Table 3. Non -CIP PPSELD c lients
2020-2021 2020 2021
Customers Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan
Residential 13,546 13,551 13,535 13,515 13,477 13,497 13,508 13,468 13,411 13,376 13,345 13,317
Commercial 211 200 196 196 197 197 195 200 202 209 211 215
NRECA International Page 3
Org. Public 33 34 34 34 34 33 36 36 36 35 36 36
Org. Autonomy 62 62 62 63 63 63 66 68 69 71 71 71
Tax Exempt 3 3 3 3 3 3 3 3 3 3 3 3
General power 27 29 29 29 29 29 50 55 55 67 66 66
Primary-volt
consumers 4 4 4 4 4 4 4 4 4 4 4 4
Other - - - - - - - - - - - -
Total 13,886 13,883 13,863 13,844 13,807 13,826 13,862 13,834 13,780 13,765 13,736 13,712
2021-2022 2021 2022
Customers Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan
Residential 13,278 13,279 13,247 13,244 13,270 13,276 13,329 13,360 13,383 13,423 13,486 13,504
Commercial 216 220 222 228 229 232 239 242 246 249 254 258
Org Public 36 36 36 36 36 36 36 36 38 39 40 41
Org Autonomy 71 71 72 72 72 72 72 71 72 74 75 76
Tax Exempt 3 3 3 3 3 3 3 3 3 3 3 3
General power 66 66 66 66 66 66 65 67 69 68 68 69
Primary-volt
consumers 3 3 3 3 3 3 3 3 3 3 3 3
Other - - - - - - - - - - -
Total 13,673 13,678 13,649 13,652 13,679 13,688 13,747 13,782 13,814 13,859 13,929 13,954
The client’s penetration rate by municipality is illustrated in Table 4 for February 2020. Forty-
one percent of households are connected to PPSELD electricity service in the five communes.
Table 4. Penetration rate by commune
Total Client Base Outside CIP
February 2020
Clients
Penetration
Rate
Households
Commune
Caracol 2,245 125% 1,800
Trou-du-Nord 6,030 66% 9,204
Sainte Suzanne 301 5% 5,560
Terrier Rouge 1,704 27% 6,326
Limonade 3,606 33% 10,840
Total 13,886 41% 33,730
The PPSELD distribution system does not cover all parts of the five communes, this is why the
penetration rate in some of them is still low. It is estimated that around than 90% of the clients with the area of influence of PPSELD transformers are connected to P PSELD service.
Electricity delivered, sales and losses
The figure 1 below presents electricity generated and distributed by the PPSELD power plant and through the distribution system for the contract period. Figure 1 also differentiates electricity sold to CIP clients and that sold to residential and commercial clients outside CIP. Over this period,
39% of the of the electricity was sold to CIP clients, 49% sold to residential and commercial clients
with 12% losses.
NRECA International Page 4
Figure 1. Net generation, e lectricity s ales and electricity l osses
Electricity sales
Electricity sales were registered throughout PSELD -T for CIP (industrial) clients, residential and
commercial clients. Electricity rates are denominated in dollars for industrial clients inside CIP
and in HTG for residential and commercial clients outside the park.
Sales to industrial clients
Sales of electricity to industrial clients increased as some clients increased activities that resulted
in higher demand . The company with the highest consumption accounts for 35% of electricity
sales and 70% of all industrial sales. Table 6 illustrates industrial electricity sales by month and
year in MWh.
Table 6 Industrial sales by month in MWh.
Energy Sold inside CIP - Industrial Clients
Feb-20 Mar-20 Apr-20 May-20 Jun-20 Jul-20 Aug-20 Sep-20 Oct-20 Nov-20 Dec-20 Jan-21
740 627 380 773 930 1,025 1,021 1,034 967 821 464 709
Feb-21 Mar-21 Apr-21 May-21 Jun-21 Jul-21 Aug-21 Sep-21 Oct-21 Nov-21 Dec-21 Jan-22
604 787 808 865 925 780 1,045 1,017 906 864 549 387
740
627
380
773
930
1,025 1,021 1,034
967
821
464
709
604
787 808
865
925
780
1,045 1,017
906 864
549
387
720
703
799
953
1,040
965
1,060 1,004 1,101
1,037
772
927
775
754
923
1,026
1,096
1,147
1,118
1,290
1,188
1,097
878
1,057
228
254
305
231
214
375
269
266 202
33
288
89
194
320
225
283
257
330
369
189
208
154
335
88
-
200
400
600
800
1,000
1,200
1,400
1,600
1,800
2,000
2,200
2,400
2,600
Thousands
Net generation, electricity sales and electricity losses [kWh]
Sales inside CIPSales outside CIPTotal Electricity losses
NRECA International Page 5
Residential and commercial sales
With the increase in residential and commercial consumers served by PSELD-T, sales to these
consumers increased significantly. While sales to industrial clients remain significant, residential
and commercial sales account for more than half of all PPSELD sales. Table 7 illustrates the
progression of sales in MWh per year, while Figure 2 provides a similar illustration of sales per
month during the last two year of residential and commercial sales. Residential sales represent
87% of sales while commercial clients consume 6% and other clients – such as public facilities,
represent 7% of electricity sales.
Table 7 Electricity sales in MWh , Feb 2020 – Jan 2022.
Customers
2020 2021
Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan
Residential 549 555 640 783 855 796 857 798 850 811 597 742
Commercial 65 58 68 91 108 89 82 66 77 64 52 64
Organization Public 8 9 10 14 13 14 15 14 13 13 8 10
Organization Autonomy 18 18 17 17 18 13 20 20 24 24 18 21
Tax Exempt 10 11 12 5 1 1 1 1 1 2 1 2
General power 24 30 39 38 41 47 79 85 98 101 75 77
Primary voltage
consumers 26 22 15 5 5 5 6 20 39 22 21 11
Other - - - - - - - - - - - -
Total 701 703 799 953 1,040 965 1,060 1,004 1,101 1,037 772 927
Customers
2021 2022
Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan
Residential 621 608 742 829 886 938 914 1,052 962 884 723 880
Commercial 49 47 60 69 75 76 71 81 76 71 55 64
Organization Public 9 10 11 14 12 12 14 18 14 7 6 6
Organization Autonomy 19 18 22 22 23 21 21 24 24 21 19 23
Tax Exempt 2 - 2 1 5 1 1 1 1 1 1 1
General power 68 65 81 84 82 85 81 90 90 90 69 78
Primary voltage
consumers 7 6 6 7 12 14 18 25 22 23 5 5
Other - - - - - - - - - - - -
Total 775 754 923 1,026 1,096 1,147 1,118 1,290 1,188 1,097 878 1,057
NRECA International Page 6
Figure 2. Industrial electricity sales in MWh by month and year.
Public l ightning
Public lighting is a service negotiated between PPSELD and each municipality to promote security
throughout the communes that are served. E lectricity consumption by street lights is evaluated
quarterly based on the number of lamps installed and the energy consumption of each lamp.
Agreements with each municipality state that PPSELD is responsible for installation of street lights
and collects fees by assessing these fees to consumers on monthly bills. Public lighting fees are a
percentage of the total electricity billed to individual consumers. . T able 8 shows the public lighting
consumption per month from February 2021 to January 2022.
-
200
400
600
800
1,000
1,200
1,400
MWh
Electricity Sales -Non CIP (MWh)
2013 2014 2015 2016 2017
2018 2019 2020 2021 2022
NRECA International Page 7
Table 8. Consumption in MWh per month
Commune
2021 2022
Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan
Caracol 4.30 4.76 4.60 4.76 4.60 4.76 4.76 4.60 4.76 4.60 4.76 4.76
Ekam 1.74 1.92 1.86 1.92 1.86 1.92 1.92 1.86 1.92 1.86 1.92 2.27
Trou du Nord 12.24 13.55 13.11 13.55 13.11 15.37 15.37 14.87 15.37 14.87 15.37 15.37
Sainte Suzanne 0.93 1.03 0.99 1.03 0.99 1.03 1.03 0.99 1.03 0.99 1.03 1.03
Terrier Rouge 4.07 4.51 4.37 4.51 4.37 4.51 4.51 4.37 4.51 4.37 4.51 5.34
Limonade 5.49 6.08 5.88 6.08 5.88 6.08 6.08 5.88 6.08 5.88 6.08 6.08
28.76 31.85 30.82 31.85 30.82 33.67 33.67 32.58 33.67 32.58 33.67 34.84
Tariffs
During the PSELD-T transition period, tariffs remained unchanged as directed by USAID.
USAID and the GoH made this decision to avoid creating social unrest. Table 9 illustrates the rate
schedule applied during the last two years.
Table 9. PSELD -T rate schedule applied through 2022
Category Charge Unit Rate Comments
Customer located outside the Caracol Industrial Park
Residential consumers, 120 V service
R Fixed charge Gds/month 207.00
Variable charges
0-30 kWh Gds/kWh 16.84
31-200 kWh Gds/kWh 22.39
>200 kWh Gds/kWh 31.16
Residential consumers, 240 V service
R240 Fixed charge Gds/month 207.00
Variable charge – all consumption Gds/kWh 32.37
Commercial consumers, 120 V service
C Fixed charge Gds/month 207.00
Variable charges
0-30 kWh Gds/kWh 16.84
31-200 kWh Gds/kWh 22.39
>200 kWh Gds/kWh 31.16
Commercial consumers, 240 V service
C240 Fixed charge Gds/month 207.00
Variable charge – all consumption Gds/kWh 32.37
Public Institutions
P Fixed charge Gds/month 207.00
Variable charge – all consumption Gds/kWh 32.37
Nonpublic Institutions
N Fixed charge Gds/month 207.00
Variable charge – all consumption Gds/kWh 32.37
Streetlights
G Fixed charge Gds/month 207.00
Variable charge – all consumption Gds/kWh 32.37
General service – Low voltage
LV Fixed charge Gds/month 207.00
Variable charge Gds/kWh 32.37
General service – Medium voltage
NRECA International Page 8
Category Charge Unit Rate Comments
MV Fixed charge Gds/month 207.00
Variable charge Gds/kWh 32.37
Other charges
New application fee Gds 500.00 All categories
Service relocation fee Gds 500.00 All categories
Account name change Gds 500.00 All categories
120V to 240V voltage change request Gds 5,800.00
Reconnection after disconnection for non-payment fee-
R, R240, C, C240, P, N and G categories Gds 200
MV and LV categories Gds 20,000
Meter test Gds 1,500 All categories
Repair fees
1
Repair of service drop cable – 120 V service Gds 4,800
Repair of service drop cable – 240 V service Gds 5,800
Repair of meter base installation– 120 V service Gds 4,700
Repair of meter base installation– 240 V service Gds 5,100
Relocate meter and meter base installation Gds 3,000
Change damaged meter Gds 4,300
Meter seal repair Gds 1,000
Replace or replace of lift pole Gds 38,800
Fraud / electricity theft penalty- Residential Gds 25,000
Fraud / electricity theft penalty- other categories Gds 50,000
Outage request Gds 18,700 All categories
Interconnection engineering study Gds 40,0000 All categories
Reimbursable security deposits
R and C categories Gds 1,500
R240 and C240 categories Gds 6,000
Other categories GDs TBD
2
Customer located inside the Caracol Industrial Park
Fixed and variable charges for all consumers
Fixed charge US$/month 10,00
Variable charge – all consumption US$/kWh 0.30
Other charges
New application fee US$ 12,00 All categories
Reconnection after disconnection for non-payment fee US$ 200.00 All categories
Outage request / US$ 200.00 Including meter test
requests
Interconnection engineering study US$ 400.00
Repair fees US$
3
Fraud / electricity theft penalty US$ 1,000
Reimbursable security deposits US$
4
All charges above are subject to 10% sales tax (TCA), except customers located inside the CIP as
well as tax exempt customers outside the CIP.
1
All categories but LV and MV
2
Based on 2 months of anticipated electricity consumption including all applicable chargers
3
Repair fees for LV and MV categories outside the park, or for all consumers inside the park, are to be determined
equally to the needed repair work on a case-by-case base, considering all labor and materials costs
4
Based on 2 months of anticipated electricity consumption including all applicable chargers
NRECA International Page 9
Customer Service - Meters reading, billing and collections.
PPSELD clients’ meters are read on a monthly basis. Customers are billed based using meter
readings to evaluate actual electricity consumption. The meter reading and billing process is as
follows:
• The service area is divided in 154 meter -reading routes. Meter technicians are assigned to
specific routes to read meters and deliver bills. Meter technician read the meter, enter the
reading in a tablet computer and print the
bill on site to deliver to the client.
• Meters are read each month.
• All meters in a route are read on the same day.
• The collected readings are updated in CIS. Commercial department staff review and
confirm bills issued by technicians in the field.
• Large CIP consumers and some larger institutions receive bills via email.
• Payments are due 14 days after the meter is read.
Figure No 3 illustrates the activities of the reading, billing, and billing delivery to the client.
Customers may pay bills at any PPSELD office or collection point that are interconnected to the
CIS. Walk-in customers interact with PPSELD customer service representatives who receive
payment and provide a receipt for the transaction. The larger customers can transfer funds via
direct deposit to the PPSELD bank account.
Cash received at PPSELD collection points is counted and prepared for deposit after the office is
closed to the public. A cash reconciliation is carried out the next morning at the PPSELD main
offices to ensure the amounts counted and received are correct. After reconciliation, payments are
recorded in the system, and cash is deposited.
NRECA International Page 10
Figure 3. Meter reading, billing, and bill delivery on site
Reading the meter Processing the bill
Printing the bill Delivering the bill to the client
Web CIS
The webCIS is composed of eight modules including an administration module, a customer
management module, a billing module, a cashier module, an accounting module, an energy
management module, a user management module and a reporting module. The webCIS is
designed to interface with customer service personnel via a web application. All users connect to
the CIS through an internal network or remotely. No other applications are required on user’s
laptop to connect to the CIS. The modules have the following features.
Administration module
NRECA International Page 11
o Tariff definition, tariff charges and fee set up, including definition of streetlight
surcharges
o Definition and management of accounting codes for billing and collection transactions
o Creation and management of meter reading routes
o Set up and management of poles, transformers, and routes
o Management and set up of field offices and collection points
Customer Management module
o Customers’ information data (name, address, phone, etc.)
o Management of customers’ account data, including tariff, location, pole and
transformer linkage, route, tariff, etc.
o Management of meters including location, status (energized, disconnected, etc.)
o Customers’ general ledger
o Management of meter installation order (Meter Order) includes all steps required to
install or remove a meter at a customer’s premise.
o Management of service orders
o Management of customer complains
Billing module
o Billing of routes, including meter reading, billing, and noting abnormalities and
printing of bills.
o Generation of meter disconnection lists for non- payment and meter reconnection lists
o Management of do-not-disconnect list
o Management and oversight of adjustments to customer’s general ledger (credits or
debits)
o Management and oversight of fraud fees
Cashier module
o Receiving customers’ payment and printing of payment receipts
o Customer reimbursement module and printing of payment receipts
o Collection summaries for reconciliation of cash collection by office and customer
service representatives
Accounting module
o Reports of transactions for billing and collection revenues
o Generation of daily and monthly transaction summaries
Reporting module
o Several reports of electricity sales, billing and collection used for operations
Energy balance module by distribution transformer
User management module
o Management of user attributes, hierarchies and security level, and activity log.
District offices
PPSELD has established offices strategically located to allow customers to request service
connections, pay bills, register complaints, or just seek information from PPSELD customer
service agents. Customer service personnel receive consumers, attend to customer requirements,
and receive payments for electricity consumption. The offices are open from Monday to Friday
from 7:30 a.m. to 3:30 p.m. and on Saturdays from 8:00 a.m. to 12:00 p.m.
NRECA International Page 12
To facilitate consumer payments, a network of collection points operated by third parties was
established to facilitate customer payments. PPSELD representatives at these collection points
are able to access the CIS to provide billing information and record payments. The payment agents
receive a fixed payment per invoice collected. Figure 4 illustrates a map of the PPSELD district
offices and third party collection agents.
Figure 4. Location of PPSELD c ommercial services offices.
Task 2 Operate and maintain the 10 MW generation plant,
distribution grid, and ancillary equipment
Electricity power g eneration plant
The CIP power plant consists of six generating units, each of which has a maximum capacity of
1.7 MW. These generators are designed to burn heavy fuel oil or diesel fuel, depending on fuel
availability and cost. The plant was designed and built by ESD Engineering and Service SRL under
contract with USAID.
The generation department cons ists of operations and maintenance teams. The operations team
includes three groups of four operators. The groups work rotating twelve-hour shifts to provide a
24-hour service. The operators were trained to operate all the generation units, the boiler
equipment and the fuel tank farm. NRECA advisors, managers, and safety coordinator supervise
NRECA International Page 13
all operations and maintenance activities at the power plant as well as provide periodic training of
the generation team.
The maintenance team is composed of mechanical and electrical teams . The two maintenance
teams are responsible for maintaining and repair of the power plant to ensure the availability of all
components in the plant. The generation maintenance personnel perform preventive and corrective
maintenance following manufacturer instructions for all the equipment installed in the plant,
including six generators and auxiliary equipment. The result of the generation team has been
outstanding; the PPSELD plant is recognized as the most reliable plant in Haiti with an a vailability
index of 99.56% for January 2022. Table 10 illustrates plant production for the PSELD-T
performance period. Table 11 illustrates the maximum demand for each month of the performance
period.
Table 10 Total G ross Production per Month – kWh
0
500,000
1,000,000
1,500,000
2,000,000
2,500,000
3,000,000
Feb-20Mar-20 Apr-20May-20 Jun-20 Jul-20Aug-20 Sep-20 Oct-20Nov-20 Dec-20 Jan-21
Production1,817,4951,717,6581,612,6362,107,2992,336,4722,528,6272,512,1482,464,6152,433,6242,042,9561,665,9781,875,462
0
500,000
1,000,000 1,500,000 2,000,000 2,500,000
3,000,000
Feb-21Mar-21 Apr-21May-21 Jun-21 Jul-21Aug-21 Sep-21 Oct-21Nov-21 Dec-21 Jan-22
Production1,706,4702,012,0122,103,6552,330,1862,436,2932,414,9272,704,5492,659,7262,462,7672,266,3331,900,2791,658,695
NRECA International Page 14
Table 11. Total Plant Max Demand per Month kW
During the period of February 2020 through January 2022, electricity generation reached 51.7
GWh while the fuel consumption was approximately 3.3 million gallons, diesel and HFO. In
average 15.66 kWh per gallon of fuel was produced.
The maximum demand registered in the same period was in the month of September 2021, 6,575
kW. Figure 5 illustrates the demand by year and month throughout the last five years of PPSELD
operation.
0
1,000
2,000
3,000
4,000
5,000
6,000
7,000
Feb-20Mar-20Apr-20May-20Jun-20Jul-20Aug-20Sep-20Oct-20Nov-20Dec-20Jan-21
Peak Load5,8285,8684,8655,8846,2716,3516,4766,4776,4455,9585,6025,625
0
1,000 2,000 3,000 4,000 5,000 6,000 7,000
Feb-21Mar-21Apr-21May-21Jun-21Jul-21Aug-21Sep-21Oct-21Nov-21Dec-21Jan-22
Peak Load5,6065,4595,8085,9386,3346,4046,5166,5756,4136,3415,9145,818
NRECA International Page 15
Figure 5. P eak plant demand
Preventive maintenance
The power generation station consists of six 4- stroke, vertical, direct injection, single acting and
trunk piston type generators with turbocharger and inter- cooler. These six units are containerized.
Total hours of operation as of January 31, 2022 for each unit are shown in Table 12 below.
Table 12. Hours of operation of each generator unit
Genset Hour Meter as of January 31 , 2022
MDU NO.1 24,705
MDU NO.2 33,052
MDU NO.3 34,902
MDU NO.4 30,701
MDU NO.5 25,461
MDU NO.6 27,630
Preventive maintenance includes a combination of minor and major maintenance procedures as
prescribed by the manufacturer. Manufacturer recommendations state that minor preventive
maintenance should be performed every 3000 hours of operation while major maintenance should
be performed once every 12,000 hours. Maintenance procedures are specified for each occurrence
of minor and major maintenance. The maintenance team maintains records of all preventative and
corrective maintenance procedures undertaken for all generation units.
-
1.0
2.0
3.0
4.0
5.0
6.0
7.0
MWh
Maximum Demand (MW)
201720182019202020212022
NRECA International Page 16
Minor p reventive m aintenance
The scope of maintenance required is very similar for minor maintenance that is prescribed for
maintenance intervals of 3,000, 6,000, 9,000, 15,000, 18,000, and 21,000 hours . These
maintenance procedures include inspection of all top- end (compression chamber) components of
the engine, replacement of the injection nozzles if heavy fuel oil has been used, and repair of all
issues identified in the inspection process.
Inspection procedures require inspection of the axial clearance of the crankshaft, confirmation
torque settings for connecting rods; inspection of the main/big end bearings and the timing gear
and other related inspection procedures. In addition, minor electrical preventive maintenan ce
procedures are performed according to the manufacturer’s recommendations. Table 13
summarizes the dates when minor maintenance was performed.
Table 13. Minor Preventat ive Maintenance
Minor Preventive Maintenance Performed during the Project
Feb/2020 to Jan/2022
Genset 18000 hrs. 21000 hrs. 27000 hrs. 30000 hrs.
MDU No1 August 2,020 June 2,021
MDU No2 August 2,021 November 2,020 August 2,021
MDU No3 May 2,021
MDU No4 June 2,21
MDU No5 April 2,020 February 2,021
MDU No6 March 2,020 January 2,022
Major preventive m aintenance
Major preventative maintenance is required every 12,000 hours of generator operation. The
manufacturer recommendations require that all components of the generator must be thoroughly
inspected to identify any anomalies in major systems or components. The inspection considers any
anomalies identified in the operating record to guide the inspection and discovery process.
Manufacturer recommendations also include replacement of bearings, injectors, oil and
compression rings, and other major components. Service technicians are required to measure major
and minor components to determine if they are within proper operating specifications – and to
replace components that are outside of operating compliance. With respect to electrical
maintenance, major maintenance procedures are also specified in the manufacturer guidebooks.
Service technicians are required to ensure that the engine is left in optimal condition at the
conclusion of major maintenance processes. T able 14 shows the dates when major maintenance
was performed for the six genset units.
Table 14. Gensets Major Preventive Maintenance
Gensets Major Preventive Maintenance Feb/2020 to Jan/2022
Genset 24000 Hrs.
MDU No1
MDU No2 January 2,020
NRECA International Page 17
MDU No3 August 2.020
MDU No4 October 2,020
MDU No5
MDU No6 April 2,021
*200 hrs. inspection is performed after a major maintenance
Ancillary E quipment
Like all equipment installed in the plant, auxiliary equipment plays an important role in the
operation of PSELD power plant. PPSELD team members carried out the respective maintenance
to ensure that they operate efficiently and effectively to ensure their continued availability. Air
compressors required to initiate diesel/HFO starting conditions, as well as to produce compressed
air for the instrumentation system, are inspected daily. If problems are noted, maintenance is
scheduled immediately. Other components that are inspected daily include engine oil centrifuges;
HFO centrifuges; and the exhaust gas recovery boiler that produces the steam to heat HFO. This
boiler is fueled by diesel and heavy fuel oil. It produces steam that is required to support continued
operation heavy fuel oil when a maintenance is required on the exhaust gas recovery boiler.
Firefighting system of the plant
An essential system for all generation plant s is the fire protection system. Fire extinguishers are
installed throughout the plant, but the primary fire suppression system is a water system that
supplies eleven fire hydrants strategically located throughout the plant. They must always be
operable therefore they are inspected routinely to ensure that they operate efficiently and
effectively to ensure their continued availability.
Other important corrective maintenance carried out during the PSELD-T project . Table 15 below
summaries additional maintenance work performed at the auxiliary equipment of the generation
plant.
Table 15. Additional Maintenance Work
Other important maintenance work performed Feb/2020-Jan/2022
Equipment Description of Work Date
HFO System Installation of new viscosity sensors and interface in HTU side 1 and 2. February 2020
Firefighting System
Replacement of defective batteries on the Diesel pump.
Maintenance of 480/220 V transformer in firefighting system.
February 2020
Genset # 1,2,3,4,5 and 6.
Coordination of electric protections and changing of parameters on the
Generator paralleling controller (GPC’s).
May 2020
LO separator # 1 Major maintenance July, 2020
Steam exchanger # 2 Corrective maintenance on HFO booster system # 2 July, 2020
MDU No. 1 Corrective maintenance on cylinder head No. 5. July, 2020
MDU No. 3 Corrective maintenance on injection pumps cylinders #7 and #8 September 2020
MDU No. 1
Change of oil scrapper and compression rings on all cylinders due high oil
consumption
December 2020.
Air compressor # 1 Major maintenance February 2021
Steam exchanger # 1 Corrective maintenance on HFO booster system # 1 May 2021
MDU No. 4 Preventive maintenance on turbocharger September 2021
NRECA International Page 18
Laboratory tests
During the 24-month period of PSELD-T implementation, routine tests have been carried out on a
periodic basis to evaluate power plant performance and identify potential maintenance
requirements. Monthly tests have been conducted for lubrication oil, cooling water for the six
engines and for the heavy fuel oil used in our engines. Every month exhaust gas recovery boiler
water and the auxiliary boiler were analyzed.
Electricity Distribution System
When USAID and GOH authorized expansion of service to the communes of Troud Du Nord,
Terrier Rouge, Limonade, NRECA started to rehabilitate former EdH distribution infrastructure
and to normalize former EdH consumers. F ormer EdH distribution were in a very poor conditions
in some segments requiring full replacement. Due to challenges with hiring qualified contractors
to perform distribution rehabilitation services, PPSELD trained locally hired linemen to perform
rehabilitation services. The se local staff not only gained confidence from this training experience
but also acquired the skills needed to perform maintenance work practices through the construction
training experience. P PSELD employees were trained by NRECA staff members who were
assisted in great part by NRECA member cooperative volunteers who traveled to Haiti on a
voluntary basis to provide assistance. After an intensive period of rehabilitation by January 2022,
70 km of medium voltage lines of lines were rehabilitated, and 138 km of lines were added. As
January 2022, PSELD-T have 252.86 km of lines as it is described at Table 16 below and 536
distribution transformers installed at the CIP and outside the CIP as it is shown at the T able 17,
Distribution transformers by Commune.
Table 16. PSELD -T Distribution lines by Commune
Description
Caracol
km
Troud Du
Nord
km
Saint
Suzanne
km
Tierre
Rouge
km
Limonade
km
Three phase primary lines 18.60 5.17 3.47 3.84
Single phase primary lines 8.66 3.74 5.69 1.49 2.25
Under build three phase 1.73 11.22 3.4 6.95
Under build single phase 10.87 11.62 2.44 4.78 10.64
Secondary 16.60 54.27 3.55 25.95 31.32
DCKT* 4.34
DCKT* - UB 0.27
Sub-totals 61.07 86.02 11.68 39.09 55.00
TOTAL PSELD-T 252.86
*Double circuit at CIP
NRECA International Page 19
Table 17. PSELD -T Distribution transformers by Commune
Capacity
Caracol
kVA
Troud Du
Nord
kVA
Saint
Suzanne
kVA
Tierre Rouge
kVA
Limonade
kVA
10kVA(1Ph) 24 36 1 12 12
15kVA(1Ph) 62 58 3 12 37
25kVA(1Ph) 16 59 3 21 41
37.5kVA(1Ph) 17 15 4 1 21
50kVA(1Ph) 3 3 10
75kVA(1Ph) 1 1
100kVA(1Ph) 1
30kVA(3Ph) 1
45kVA(3Ph) 6 1 2
75kVA(3Ph) 1 2
112.5kVA(3Ph) 3
150kVA(3Ph) 7
225kVA(3Ph) 20 1
300kVA(3Ph) 3 1
500kVA(3Ph) 2
750kVA(3Ph) 11
1000kVA(3Ph) 1
Sub-total 174 177 11 57 117
Total 536
Figure 6 describes the P SELD-T service area and the location of the distribution transformers.
NRECA International Page 20
Figure 6. P PSELD service area.
During this transition period, PSELD-T maintained the electricity service to its users at high
levels of reliability. The table 18. PSELD -T average service availability index below shows the
results month by month. For the year of 2020, 99.66% of reliability was recorded and for the
next year of 2021, 99.75%.
NRECA International Page 21
Table 18. PSELD -T average service availability index
2020
Month Number Outages SAIFI SAIDI
ASAI
(%)
January 11 0.60 2.30 99.69%
February 10 0.10 0.20 99.98%
March 12 6.00 1.70 99.76%
April 8 0.03 0.10 99.98%
May 42 2.10 10.70 98.57%
June 11 0.60 1.00 99.97%
July 21 0.80 2.70 99.64%
August 12 1.90 3.30 99.56%
September 12 3.10 5.30 99.27%
October 7 1.30 2.80 99.63%
November 5 0.20 0.40 99.94%
December 5 0.10 0.20 99.98%
Total/Average: 156 16.83 30.70 99.66%
2021
Month Number Outages SAIFI SAIDI
ASAI
(%)
January 6 0.80 2.20 99.70%
February 5 0.20 0.50 99.93%
March 9 0.10 0.20 99.97%
April 9 0.80 3.10 99.56%
May 11 0.40 1.40 99.82%
June 17 2.60 7.40 98.98%
July 11 1.80 2.40 99.67%
August 13 0.40 0.70 99.91%
September 10 0.80 1.40 99.81%
October 6 0.10 0.20 99.97%
November 8 0.60 1.30 99.81%
December 13 0.40 1.10 99.85%
Total/Average: 118 9.00 21.90 99.75%
2022
Month Number Outages SAIFI SAIDI
ASAI
(%)
January 13 2.90 4.70 99.37%
Note: The flooding that occurred in the Industrial Park and the PSELD generation plant - interrupted the service in
the entire PSELD-T system on the last day of January 2022.
NRECA International Page 22
Task 3. Reduce Non-technical Electricity Loss by I ncreasing Metered
Customers.
Customer normalization and connection of new clients
Once the process of rehabilitation of the medium and low voltage system was completed and the
normalization of the clients was completed, th e number of clients increased, therefore, the sales of
electricity increased and the losses began to decrease. But at the same time, the task of control of
illegal connections was initiated to continue to combat energy theft on a continuing basis. Figure
7 shows the progression of registered customers from approximately 5,000 in 2016 to
approximately 14,000 in January 2022. Although 16,502 connections were made up to January
2022, in January 2022, 13,621 customers were active and with electricity service. During the
period from February 2020 to January 2022, the number of clients ranged between 13,893 and
13,621.
Figure 7. Customers by system - January 2016 - January 2022
In the CIP, the number of customers served remain at the same level between 2020 and 2022. As
of 2022, 11 clients are in operations inside the park. See Table 2.
Table 20 below show s the number of requests for new connections received and processed
between February 2020 and January 2022. A total of 766 application were received at the offices
of PPSELD from them 759 were processed and 556 meters were connected to the service.
0
2
4
6
8
10
12
14
Jan-16 Apr-16
Jul-16
Oct-16 Jan-17 Apr-17
Jul-17
Oct-17 Jan-18 Apr-18
Jul-18
Oct-18 Jan-19 Apr-19
Jul-19
Oct-19 Jan-20 Apr-20
Jul-20
Oct-20 Jan-21 Apr-21
Jul-21
Oct-21 Jan-22
Thousands
Customers by system -last 12 months
CIPCaracolTrou du NordSte SuzanneTerrier RougeLimonade
NRECA International Page 23
Table 19. Customer Service Records
Description No of Clients/ Connections
New applications received 766
New applications processed 759
Design completed 785
Meters connected 556
Customers disconnects fraud 182
Illegal connections removed 768
Electricity loss reduction program
Electricity losses occur due to the natural heat process of the conductor as electricity is conducted
from one place to another, this phenomenon is called technical losses. Commercial losses occur
due to theft of electricity, meter manipulation and poor or improper commercial practices such as
meter reading errors, failure to deliver bills or other related commercial activities. Identification
and reduction of commercial losses is a key activity required to achieve improved financial
sustainability for electricity distribution companies. PPSELD created the r evenue protection
department to systematically and routinely identify and work to reduce electricity theft. The
revenue protection team is a permanent work unit in the commercial department comprised of
three crews of technicians who are responsible to constantly patrol the distribution network to
search for illegal connections and inspect meters. T hrough the monthly loss control of the
distribution transformers, the r evenue protection crews are organized to inspect all the transformers
with the highest losses. The distribution networks, the household connections and the meters of
the clients connected to these transformers are inspected everyday including weekends. Activities
performed by the revenue protection crews include:
- Patrol the distribution network in search of illegal taps
- Inspection of meter bases and service drops in search for hidden meter bypasses
or tampered meters
- Sweep inspections on identified trouble areas with higher losses
- Disconnection of consumer from pole found consuming electricity illegally
- Disconnect and connect areas of the system that were temporally suspended due
to damages on the lines due to theft actions.
- Disconnect and remove illegal connections.
- Removal of meters and service drops from customers disconnected for non-
payment after six months.
All cases of customer fraud found are sent to the customer service department to apply a fraud fee
to the accounts of these customers. However, due to the COVID -19 pandemic during PSELD-T
implementation, the activities of the revenue protection crews were significantly restricted to avoid
contact with clients.
As Table 20 shows the results of the activities carried out by the revenue protection crews, 768
illegal connections were disconnected and 182 customers were found stealing electricity during
the period of February 2020 through January 2022. Electricity losses during the last 24 months
remained stable in the range of 11.5% percent. Losses within the CIP remained around 5%, while
NRECA International Page 24
losses outside the CIP were between 15% and 16%. Figure 8 illustrates the total losses and the
losses inside and outside the park during the last 12 months, from January 2021 to February 2022.
Figure 8. Electricity losses last 12 months average
The Figure 9 below illustrate the evolution of the losses from previous years.
4.8%5.0%4.9%4.8%4.9%4.9%5.0%5.0%5.1%5.2%5.2%5.1%5.4%5.2%
16.6%
16.2%
16.5%
15.8%16.0%16.2%
15.7%
16.3%
15.4%15.3%
16.0%16.1%15.9%
15.6%
11.6%11.5%11.7%
11.1%11.2%11.4%11.2%
11.6%
11.2%11.2%
11.5%11.6%11.7%11.5%
0%
5%
10%
15%
20%
25%
Jan-21Feb-21Mar-21Apr-21May-21Jun-21Jul-21Aug-21Sep-21Oct-21Nov-21Dec-21Jan-22Feb-22
Percentage %
% of electricity losses -last 12 months average
Losses inside CIP - 12 month average Losses outside CIP - 12 month average
Total PPSELD Losses - 12 month average Losses inside CIP - 3 month average
Losses outside CIP - 3 month average Total PPSELD Losses - 3 month average
NRECA International Page 25
Figure 9. Evolution of the electricity losses Jan 2016 – Jan 2022
Task 4 Facilitate transition to future private operator.
GOH, continuing with its strategy of privatizing the electricity service in the 10 departments of Haiti, put out to tender three departments, for which it received proposals and began a negotiation process, which showed great hope. During this process, the NRECA team provided support at the request of the USAID technical team, providing information on PSELD operations that served to
prepare the bidding documents. Multiple meetings were held to support potential proponents and the USAID-supporting contractor in this process. Unfortunately, the negotiations with the potential
candidate to operate the PSELD system did not conclude and the GoH decided to declare the tender
void in October 2021. A new process is expected to restart at the beginning of 2022.
9.5%9.6%
8.7%8.5%
8.0%
7.5%
7.2%
6.4%
5.9%5.9%5.9%5.8%5.8%
5.3%5.5%5.4%5.6%5.6%5.7%5.9%6.2%6.1%
6.5%6.7%6.8%6.9%7.0%
6.7%6.5%6.3%
5.8%
5.4%
5.0%
4.6%
4.1%
3.7%3.5%3.4%3.4%3.5%3.7%3.9%4.2%4.4%4.4%4.6%4.7%4.9%4.9%4.8%5.0%4.9%4.8%4.9%4.9%5.0%5.0%5.1%5.2%5.2%5.1%5.4%
44.9%
43.3%
43.9%
43.3%43.5%43.3%43.4%
43.1%
42.2%
40.6%40.4%
38.1%
35.5%
34.6%
32.1%
30.7%
28.8%
26.5%
24.3%
22.9%
20.7%
20.1%
19.1%
19.5%
19.0%19.0%
18.6%
19.0%
19.8%
19.3%
18.9%
19.4%19.2%19.2%19.4%
18.8%
19.2%
18.7%
19.2%
18.7%18.5%18.4%
17.8%17.6%
18.2%
18.8%
17.6%
17.2%
16.9%16.6%
16.2%
16.5%
15.8%16.0%16.2%
15.7%
16.3%
15.4%15.3%
16.0%16.1%15.9%
31.3%
30.2%30.2%
29.7%29.7%
29.4%29.2%
28.6%
27.7%
26.7%26.4%
24.8%
23.2%
22.3%
20.8%
19.9%
18.7%
17.2%
16.0%
15.3%
14.1%
13.7%
13.4%
13.7%13.5%13.5%13.4%13.5%
13.8%
13.4%
13.0%13.1%12.9%12.7%12.6%
12.0%12.2%
11.8%12.0%11.9%12.0%12.1%11.9%12.0%12.2%
12.7%
12.1%12.0%11.8%11.6%11.5%11.7%
11.1%11.2%11.4%11.2%
11.6%
11.2%11.2%
11.5%11.6%11.7%
0%
5%
10%
15%
20%
25%
30%
35%
40%
45%
50%
Sep-16 Oct-16 Nov-16 Dec-16 Jan-17 Feb-17 Mar-17 Apr-17
May-17
Jun-17
Jul-17
Aug-17 Sep-17 Oct-17 Nov-17 Dec-17 Jan-18 Feb-18 Mar-18 Apr-18
May-18
Jun-18
Jul-18
Aug-18 Sep-18 Oct-18 Nov-18 Dec-18 Jan-19 Feb-19 Mar-19 Apr-19
May-19
Jun-19
Jul-19
Aug-19 Sep-19 Oct-19 Nov-19 Dec-19 Jan-20 Feb-20 Mar-20 Apr-20
May-20
Jun-20
Jul-20
Aug-20 Sep-20 Oct-20 Nov-20 Dec-20 Jan-21 Feb-21 Mar-21 Apr-21
May-21
Jun-21
Jul-21
Aug-21 Sep-21 Oct-21 Nov-21 Dec-21 Jan-22
% of electricity losses January 2016 -January 2022
Losses inside CIP - 12 month averageLosses outside CIP - 12 month average
Total PPSELD Losses - 12 month average